Electrical Ratings [@ 77°F (25°C)]
Input Voltage: 25 VAC 50/60 Hz
Max. Input Current @ 25 VAC: 0.45 amp
Relay Load Ratings
Valve Relay: 1.5 amp @ 25 VAC 50/60 Hz 0.6 pf
Ignitor Relay: 2.0 amp @ 120 VAC 50/60 Hz (resistive)
Inducer Relay: 2.2 FLA–3.5 LRA @ 120 VAC
Circulator Relay: 14.5 FLA–25.0 LRA @ 120 VAC
Flame Current Requirements
Minimum current to insure flame detection: 1 μa DC*
Maximum current for non-detection: 0.1 μa DC*
Maximum allowable leakage resistance: 100 M ohms
*Measured with a DC microammeter in the flame probe lead
Operating Temperature Range
-40° to 175°F (-40° to 80°C)
Humidity Range
5% to 93% relative humidity (non-condensing)
Mounting
Surface mount multipoise
Dimensions
4.4” W x 5.9” H x 1.25” D